Removing and restoring power to multicarrier cabinets

Last Updated : Aug 09, 2018 |
Prolog information
  1. For a multicarrier cabinet, set the emergency transfer switch to ON.
    ADDITIONAL INFORMATION:
    This locks the PN in the emergency transfer mode until the trouble is cleared.
  2. Depending on which type of cabinet you are powering down, do one of the following:
    ADDITIONAL INFORMATION:
    • In an AC-powered multicarrier cabinet, set the circuit breaker to OFF at the power-distribution unit.
    • In a DC-powered multicarrier cabinet, turn off the DC power supply.
    • In an AC- or DC-powered single-carrier cabinet stack, turn off the power for each affected carrier individually. The ON/OFF switch is located behind the:
      • AC carrier’s WP-91153 power unit
      • DC carrier’s 676B power unit
  3. Power is restored by reversing the action taken above.
    ADDITIONAL INFORMATION:
    Restoring power will cause a restart. This process is described under EXP-PN in ABRI-POR (ASAI ISDN-BRI Port) in Avaya Aura® Communication Manager Alarms, Events, and Logs Reference.
    If a powered-down carrier contains a 676B power unit, the 676B must have been powered down for at least 10 seconds for the unit to restart.