Dell PowerEdge R660xs Environmental requirements

Last Updated : Dec 03, 2024 |

The tables in this section list the environmental requirements for the server.

Table 1: Temperature

Temperature

Specifications

Storage

–40°C to 65°C (–40°F to 149°F)

Continuous operation (for altitude <= 900 m or 2953 ft)

10°C to 35°C (50°F to 95°F) with no direct sunlight on the equipment.

Fresh air

For information about fresh air, see Expanded Operating Temperature at https://www.dell.com.

Maximum temperature gradient (operating and storage)

20°C in an hour (36°F in a hour) and 5°C in 15 minutes (9°F in 15 minutes).

Table 2: Relative humidity

Relative humidity

Specifications

Storage

58% RH with -12°C (10.4°F) minimum dew point to 80% RH with 21°C (69.8°F) maximum dew point. Atmosphere must be non-condensing at all times.

Operating

8% RH with -12°C minimum dew point to 80% RH with 21°C (69.8°F) maximum dew point. Atmosphere must be non-condensing at all times.

Table 3: Maximum vibration

Maximum vibration

Specifications

Operating

0.21 G rms at 5 Hz to 500 Hz for 10 minutes (all operation orientations).

Storage

1.88 G rms at 10 Hz to 500 Hz for 15 min (all six sides tested).

Table 4: Maximum shock

Maximum shock

Specifications

Operating

Six consecutively executed shock pulses in the positive and negative x, y, and z axes of 6 G for up to 11 ms.

Storage

Six consecutively executed shock pulses in the positive and negative x, y, and z axes (one pulse on each side of the system) of 71 G for up to 2 ms.

Table 5: Maximum altitude

Maximum altitude

Specifications

Operating

3048 m (10000 ft)

Storage

12000 m (39370 ft)

Table 6: Operating temperature de-rating

Operating temperature de-rating

Specifications

Up to 35°C (95°F)

Maximum temperature is reduced by 1°C/300 m (1.8°F/984 ft) above 900 m (2953 ft).